OPzS
OPzS
  • TECHNICIAL SPECIFICATIONS
  • PICTURES
OSP.HC
Aplications : Emergency Power, Transformer Stations, Telecom, Solar
Standarts : IEC 896-1, DIN 40736, P1
Capacity Range in Ah
: 200 - 3.000
Nominal Voltage Range
: 2V
Container Material
: SAN, Clear
GRID ALLOY

 
Pozitive : Pb+<2%Sb
Negative
: Pb+<2%Sb
Pozitive Plate
: Tubular
Negative Plate
: Grid
Electrolyte
: H2SO4, Liquid
Connector Design
: Full Insulated Bolted Connector
Current Behaviour(1-4)
: 1
Battery Life (in year)
: 20
Deisgn Life to(in year)
: 1500
CHARGING VOLTAGE IN V/Cell
:  
Fload Charge
: 2.23
Boost Charge
: 2.4
Float Charging Current/100 Ah Nominal
(20oC, Ufloat=2.23 / 2.25 V /Cell)
: 20-50 mA
Position Independent Operation Possible
: No
Water Reffilling Intervals in Year in Permanent
Float Charging/With Aqua Gen
: >3 / Not Necessary
Self Discharge of Nominal Capacity at 20oC
: ~3%
Operating Temperature Range (20 oC) : (-20/+40)
Ventilation Requirement
: with Aqua-Gen Similar to VRLA
Storage Time at 20 oC Before Refresing Charge
: 3 Months

Tab 2