Aplications |
: |
Power Plant, Transformer Stations, Signal Tower, Switch Gear, UPS, Emergency Power, Telecom |
Standarts |
: |
DIN 40738, IEC 896-1 |
Capacity Range in Ah
|
: |
75 - 2.600 |
Nominal Voltage Range
|
: |
2V |
Container Material
|
: |
SAN, Saydam |
GRID ALLOY
|
|
|
Pozitive |
: |
Pure Lead |
Negative
|
: |
Pb+<2%Sb |
Pozitive Plate
|
: |
Plante |
Negative Plate
|
: |
Grid |
Electrolyte
|
: |
H2SO4, Liquid |
Connector Design
|
: |
Full Insulated Bolted Connector |
Current Behaviour(1-4)
|
: |
4 |
Battery Life (in year)
|
: |
25 |
Deisgn Life to(in year)
|
: |
|
CHARGING VOLTAGE IN V/Cell
|
: |
|
Fload Charge
|
: |
2.23 |
Boost Charge
|
: |
2.4 |
Float Charging Current/100 Ah Nominal
(20oC, Ufloat=2.23 / 2.25 V /Cell)
|
: |
20-40 mA |
Position Independent Operation Possible
|
: |
No |
Water Reffilling Intervals in Year in Permanent
Float Charging/With Aqua Gen
|
: |
>5 / Not Necessary |
Self Discharge of Nominal Capacity at 20oC
|
: |
~3% |
Operating Temperature Range (20 oC) |
: |
(-20/+40) |
Ventilation Requirement
|
: |
with Aqua-Gen Similar to VRLA |
Storage Time at 20 oC Before Refresing Charge
|
: |
3 Months |