NET.POWER
NET.POWER
  • TECHNICIAL SPECIFICATIONS
  • PICTURES
net.power
Aplications : Telecom, UPS, Emergency Power,Power Supply
Standarts : IEC 896-2, BS 6290-4
Capacity Range in Ah
: 80 - 150
Nominal Voltage Range
: 12V
Container Material
: ABS,UL94-VO
GRID ALLOY

 
Pozitive : Pb+<1%Ca
Negative
: Pb+<1%Ca
Pozitive Plate
: Grid
Negative Plate
: Grid
Electrolyte
: H2SO4, Fixed in AGM
Connector Design
: Fully Insulated Bolted Connector
Current Behaviour(1-4)
: 3
Battery Life (in year)
: 12
Deisgn Life to(in year)
:  
CHARGING VOLTAGE IN V/Cell
:  
Fload Charge
: 2.25
Boost Charge
: 2.4
Float Charging Current/100 Ah Nominal
(20oC, Ufloat=2.23 / 2.25 V /Cell)
: 10-40 mA
Position Independent Operation Possible
: Yes 
Water Reffilling Intervals in Year in Permanent
Float Charging/With Aqua Gen
: 10-40mA
Self Discharge of Nominal Capacity at 20oC
: 2-3%
Operating Temperature Range (20 oC) : (-20/+40)
Ventilation Requirement
: VRLA Regulation: EN 50272-2
Storage Time at 20 oC Before Refresing Charge
: 6 Months

Tab 2